Abstract
A study of tubular bubble absorption in a NH3-H2O solution and its application to the generator-absorber heater exchange absorption cycle (GAX) was performed. Design conditions for a compact bubble absorber, which included GAX load, NH3 vapor to be absorbed, and coolant energy quality for GAX purposes, and geometric constraints for a 1-ton refrigeration unit were determined. The performance of a first generation absorber design was determined experimentally. A second generation absorber was then designed, based on first generation experimental results. The second generation design employed judiciously chosen techniques for both heat and mass transfer enhancement. Heat transfer augmentation was achieved by repeated roughness, internal spacers, and increased thermal conductivity metal for absorber construction. Mass transfer augmentation was achieved through internal static mixers, variable cross-section flow areas, and numerous vapor injector designs. Performance of this second generation absorber was analyzed and possible directions for further improvement discussed.
Original language | English (US) |
---|---|
Title of host publication | Proceedings of the International Absorption Heat Pump Conference |
Publisher | Publ by ASME |
Pages | 217-223 |
Number of pages | 7 |
ISBN (Print) | 0791806987 |
State | Published - Jan 1 1994 |
Event | Proceedings of the International Absorption Heat Pump Conference - New Orleans, LA, USA Duration: Jan 19 1994 → Jan 21 1994 |
Other
Other | Proceedings of the International Absorption Heat Pump Conference |
---|---|
City | New Orleans, LA, USA |
Period | 1/19/94 → 1/21/94 |
All Science Journal Classification (ASJC) codes
- General Engineering