T1 - Comparing airborne infectious aerosol exposures in sparsely occupied large spaces utilizing large-diameter ceiling fans
AU - Yang, Senwen
AU - Wang, Liangzhu (Leon)
AU - Raftery, Paul
AU - Ivanovich, Michael
AU - Taber, Christian
AU - Bahnfleth, William P.
AU - Wargocki, Pawel
AU - Pantelic, Jovan
AU - Zou, Jiwei
AU - Mortezazadeh, Mohammad
AU - Shu, Chang
AU - Wang, Runzhong
AU - Arnold, Scott
N1 - Publisher Copyright:
© 2023 Elsevier Ltd
PY - 2023/3/1
Y1 - 2023/3/1
N2 - In sparsely occupied large industrial and commercial buildings, large-diameter ceiling fans1 (LDCFs) are commonly utilized for comfort cooling and destratification; however, a limited number of studies were conducted to guide the operation of these devices during the COVID-19 pandemic. This study conducted 223 parametrical computational-fluid-dynamics (CFD) simulations of LDCFs in the U.S. Department of Energy warehouse reference building to compare the impacts of fan operations, index-person, and worker-packing-line locations on airborne exposures to infectious aerosols under both summer and winter conditions. The steady-state airflow fields were modeled while transient exposures to particles of varying sizes (0.5–10 μm) were evaluated over an 8-h period. Both the airflow and aerosol models were validated by measurement data from the literature. It was found that it is preferable to create a breeze from LDCFs for increased airborne dilution into a sparsely occupied large warehouse, which is more similar to an outdoor scenario than a typical indoor scenario. Operation of fans at the highest feasible speed while maintaining thermal-comfort requirements consistently outperformed the other options in terms of airborne exposures. There is no substantial evidence that fan reversal is beneficial in the current large space of interest. Reversal flow direction to create upward flows at higher fan speeds generally reduced performance compared with downward flows, as there was less airflow through the fan blades at the same rotational speed. Reversing flow at lower fan speeds decreased airflow speeds and dilution in the space and, thus, increased whole-warehouse concentrations.
AB - In sparsely occupied large industrial and commercial buildings, large-diameter ceiling fans1 (LDCFs) are commonly utilized for comfort cooling and destratification; however, a limited number of studies were conducted to guide the operation of these devices during the COVID-19 pandemic. This study conducted 223 parametrical computational-fluid-dynamics (CFD) simulations of LDCFs in the U.S. Department of Energy warehouse reference building to compare the impacts of fan operations, index-person, and worker-packing-line locations on airborne exposures to infectious aerosols under both summer and winter conditions. The steady-state airflow fields were modeled while transient exposures to particles of varying sizes (0.5–10 μm) were evaluated over an 8-h period. Both the airflow and aerosol models were validated by measurement data from the literature. It was found that it is preferable to create a breeze from LDCFs for increased airborne dilution into a sparsely occupied large warehouse, which is more similar to an outdoor scenario than a typical indoor scenario. Operation of fans at the highest feasible speed while maintaining thermal-comfort requirements consistently outperformed the other options in terms of airborne exposures. There is no substantial evidence that fan reversal is beneficial in the current large space of interest. Reversal flow direction to create upward flows at higher fan speeds generally reduced performance compared with downward flows, as there was less airflow through the fan blades at the same rotational speed. Reversing flow at lower fan speeds decreased airflow speeds and dilution in the space and, thus, increased whole-warehouse concentrations.
UR - http://www.scopus.com/inward/record.url?scp=85147330406&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85147330406&partnerID=8YFLogxK
U2 - 10.1016/j.buildenv.2023.110022
DO - 10.1016/j.buildenv.2023.110022
M3 - Article
AN - SCOPUS:85147330406
SN - 0360-1323
VL - 231
JO - Building and Environment
JF - Building and Environment
M1 - 110022
ER -