TY - JOUR
T1 - Simulation-based assessment of ASHRAE Guideline 36, considering energy performance, indoor air quality, and control stability
AU - Faulkner, Cary A.
AU - Lutes, Robert
AU - Huang, Sen
AU - Zuo, Wangda
AU - Vrabie, Draguna
N1 - Publisher Copyright:
© 2023 Elsevier Ltd
PY - 2023/7/15
Y1 - 2023/7/15
N2 - This study assesses American Society of Heating, Refrigerating and Air-Conditioning Engineers Guideline 36 (G36) with a typical medium office building. Specifically, this study employed a Modelica model of a variable air volume (VAV) system that serves this building, which includes components for representing indoor virus transmission and filtration. It then implemented the G36 control sequences for both water-side and air-side equipment in Python. After that, this study conducted the assessment by co-simulating G36 and the Modelica model using the Building Operations Testing Framework. Unlike existing works, this work has three unique features: (1) It considers the interactions between control sequences for water-side and air-side equipment of the studied VAV system. (2) It assesses the performance of G36 from the perspective of IAQ. (3) It examines the short-term behaviors of the studied building under G36 to understand the control stability. This assessment confirms significant energy savings from G36, largely because of the interaction between supply air temperature and hot water controls. It also reveals a trade-off between the ability to slow the spread of virus and the energy performance via demand controlled ventilation. Lastly, it emphasizes the necessity of tuning local feedback control when implementing G36.
AB - This study assesses American Society of Heating, Refrigerating and Air-Conditioning Engineers Guideline 36 (G36) with a typical medium office building. Specifically, this study employed a Modelica model of a variable air volume (VAV) system that serves this building, which includes components for representing indoor virus transmission and filtration. It then implemented the G36 control sequences for both water-side and air-side equipment in Python. After that, this study conducted the assessment by co-simulating G36 and the Modelica model using the Building Operations Testing Framework. Unlike existing works, this work has three unique features: (1) It considers the interactions between control sequences for water-side and air-side equipment of the studied VAV system. (2) It assesses the performance of G36 from the perspective of IAQ. (3) It examines the short-term behaviors of the studied building under G36 to understand the control stability. This assessment confirms significant energy savings from G36, largely because of the interaction between supply air temperature and hot water controls. It also reveals a trade-off between the ability to slow the spread of virus and the energy performance via demand controlled ventilation. Lastly, it emphasizes the necessity of tuning local feedback control when implementing G36.
UR - http://www.scopus.com/inward/record.url?scp=85160576843&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=85160576843&partnerID=8YFLogxK
U2 - 10.1016/j.buildenv.2023.110371
DO - 10.1016/j.buildenv.2023.110371
M3 - Article
AN - SCOPUS:85160576843
SN - 0360-1323
VL - 240
JO - Building and Environment
JF - Building and Environment
M1 - 110371
ER -