Abstract

Using computational fluid dynamics simulations of an occupant in a ventilated room, we find that breathing zone ozone levels can be substantially lower and ozone reaction products associated with human surfaces (ORPHS) levels considerably higher than room levels. For air exchange rates <3-h, the ratio of the breathing zone to the ozone concentration 1 m from the body (bulk air), rozone, ranges from 0.59 to 0.75 for floor or ceiling air supply. ORPHS are enriched in the breathing zone, with concentrations for these conditions ranging from 1.2 to 2.5 greater than bulk air concentrations. At high air exchange rates (>8-h), the breathing zone concentrations approach bulk air concentrations (rozone > 0.9) with a floor supply, whereas large concentration gradients occur between breathing zone and bulk air with a ceiling supply. At these high air exchange rates, ORPHS levels are 1.6-2.0 and 2.9-6.0 times the bulk air concentrations for floor and ceiling supply, respectively. The extent of depletion of ozone or enrichment of ORPHS is large enough that reliance on micro-environmental measurements alone, to assess the intake of ozone or ORPHS, is undesirable.

Original languageEnglish (US)
Pages (from-to)324-334
Number of pages11
JournalIndoor Air
Volume19
Issue number4
DOIs
StatePublished - Aug 2009

All Science Journal Classification (ASJC) codes

  • Environmental Engineering
  • Building and Construction
  • Public Health, Environmental and Occupational Health

Fingerprint

Dive into the research topics of 'The influence of chemical interactions at the human surface on breathing zone levels of reactants and products'. Together they form a unique fingerprint.

Cite this